==> picture [514 x 393] intentionally omitted <==
----- Start of picture text -----
% 7467VillageSouth ofRedBroadway,Hook WaterRed Hook, & NewWastewater Treatment York 12571 ea 3 nviramarnta 04/04/2023 Consulting Water System Wastewater System Water System Notes: Wastewater System Notes: Sample results for February 2023, with reporting submitted on or before March 28, 2023. . Monthly All monthly coliform tests were completed with Required Samples Result Compliance Total Coliform no presence of coliform or e. coli BOD <4.0 February 2023 Tss 44 10 mg/L NH3 <0.5 1.81 mg/L Fecal Coliform <1.0 200/100 mL Deficiencies Deficiencies Well Control Issues 2020Waitingtest for indicatedSCADA update this was not a viable option for Village flow oe CurrentlyUren. ; aaMedoraMeaora mixermixer inin . ¥placepiaceatoto keepkee,7 AnoxicOXI tankTank SOUGSsolid . . . 7 . . moving. May need to consider this in future updates. Town/Village interconnect in case of emergency. Engineering review currently in place. Weil level monitors have been reviewed with a variety of repairs Well Level/Flow that were required. Currently looking at options for Sand Filter Rebuild Sand Filters have never been rebuilt or media replaced. Should cammunication to wells 14 & 15 as there is a short in wiring price and schedule for the nearfuture. between the plant and the wells Train Down for Review One process i is down for review of deficiencies. Review ta be completed this week and sentfor review. Pump Station Pump Station pumps clogging issues have been an issue for some time. Pump Station mixing should be implemented to help with pump failure and pump station pump outs. Backflow Prev. Replacement Facilities backflow Preventor in need of replacement. For Future Notes: ----- End of picture text -----