Village of Red Hook Water Treatment Facilities Monthly Report
November 1, 2024
System Flow
During the month of October the water treatment facility treated 7,484,117 total gallons, which is an average of 241,423 gallons per day. See below for the Annual Daily Average Flow Chart:
All bacteriological samples for the month were collected and transported to York Analytical, Newton, Connecticut. Please see below for sample locations and results:
| Location | Total Coliform | E. Coli | |||
|---|---|---|---|---|---|
| Traditions Mail Room | Absent | Absent | |||
| 2 W Market | Absent | Absent | |||
| 16 Kent | Absent | Absent |
Chemical Usage
During the month of September, the water treatment plant used 75 gallons of sodium hypochlorite. The average daily use was 2.4 gallons per day.
If you should have any questions in regards to this report, please feel free to reach out to me at our main office at (845) 244-0129 or by email at Fernando@C3NDEnviro.com
Sincerely, Fernando Dongo Principal Consultant C3ND Environmental Consulting
Water Systems Operation Report Microbiological Sample Results
NEW YORK STATE DEPARTMENT OF HEALTH
Bureau of Water Supply Protection
|NEW YORK STATE DEPARTMENT OF HEALTH Water Systems Operation Report Bureau of Water Supply Protection Microbiological Sample Results|NEW YORK STATE DEPARTMENT OF HEALTH Water Systems Operation Report Bureau of Water Supply Protection Microbiological Sample Results|NEW YORK STATE DEPARTMENT OF HEALTH Water Systems Operation Report Bureau of Water Supply Protection Microbiological Sample Results|NEW YORK STATE DEPARTMENT OF HEALTH Water Systems Operation Report Bureau of Water Supply Protection Microbiological Sample Results|NEW YORK STATE DEPARTMENT OF HEALTH Water Systems Operation Report Bureau of Water Supply Protection Microbiological Sample Results|NEW YORK STATE DEPARTMENT OF HEALTH Water Systems Operation Report Bureau of Water Supply Protection Microbiological Sample Results|NEW YORK STATE DEPARTMENT OF HEALTH Water Systems Operation Report Bureau of Water Supply Protection Microbiological Sample Results|NEW YORK STATE DEPARTMENT OF HEALTH Water Systems Operation Report Bureau of Water Supply Protection Microbiological Sample Results|NEW YORK STATE DEPARTMENT OF HEALTH Water Systems Operation Report Bureau of Water Supply Protection Microbiological Sample Results|NEW YORK STATE DEPARTMENT OF HEALTH Water Systems Operation Report Bureau of Water Supply Protection Microbiological Sample Results|NEW YORK STATE DEPARTMENT OF HEALTH Water Systems Operation Report Bureau of Water Supply Protection Microbiological Sample Results|NEW YORK STATE DEPARTMENT OF HEALTH Water Systems Operation Report Bureau of Water Supply Protection Microbiological Sample Results| |---|---|---|---|---|---|---|---|---|---|---|---| ||||||||||||| |Public Water System Name||||Reporting Month/Year||Date Report Submitted|||Source Water Type(s)||| |Village of Red Hook||||Oct-24||11/1/24|||☐Surface ☒Ground ☐GWUDI||| |Public Water System ID||||County||Town, Village, or City|||☐Purchase with subsequent chlorination||| |NY1302775||||Dutchess||Red Hook|||☐Purchase w/out subsequent chlorination||| |DATE|Source(s) in Use|Treated water volume (gallons/day)|Chlorination||||Comments/Observations||||| ||||||Liquid|Free chlorine residual at entry point (mg/l)|||||| ||||||Hypochlorite added to crock (quarts)||||||| |1|Well 1,3,4,9,12,15|188,026|||52.00|1.3|||||| |2|Well 1,3,4,9,12,15|417,953||||1.4|||||| |3|Well 1,3,4,9,12,15|142,457||||1.3|||||| |4|Well 1,3,4,9,12,15|224,816|||40.00|1.4|||||| |5|Well 1,3,4,9,12,15|250,180||||1.2|||||| |6|Well 1,3,4,9,12,15|204,300||||1.4|||||| |7|Well 1,3,4,9,12,15|321,384||||0.7|||||| |8|Well 1,3,4,9,12,15|383,039|||40.00|0.4|||||| |9|Well 1,3,4,9,12,15|86,902|||20.00|0.5|||||| |10|Well 1,3,4,9,12,15|276,487||||1.4|||||| |11|Well 1,3,4,9,12,15|143,056|||20.00|1.5|||||| |12|Well 1,3,4,9,12,15|290,551||||1.2|||||| |13|Well 1,3,4,9,12,15|228,021||||1.2|||||| |14|Well 1,3,4,9,12,15|180,450|||40.00|0.8|||||| |15|Well 1,3,4,9,12,15|172,785||||0.8|||||| |16|Well 1,3,4,9,12,15|262,720|||40.00|1.0|||||| |17|Well 1,3,4,9,12,15|246,851||||1.0|||||| |18|Well 1,3,4,9,12,15|231,179|||28.00|1.0|||||| |19|Well 1,3,4,9,12,15|253,304||||1.2|||||| |20|Well 1,3,4,9,12,15|264,113||||1.2|||||| |21|Well 1,3,4,9,12,15|268,647|||24.00|0.5|||||| |22|Well 1,3,4,9,12,15|228,636||||0.7|||||| |23|Well 1,3,4,9,12,15|273,950|||48.00|0.6|||||| |24|Well 1,3,4,9,12,15|214,100||||0.9|||||| |25|Well 1,3,4,9,12,15|246,921|||40.00|1.1|||||| |26|Well 1,3,4,9,12,15|254,452||||1.2|||||| |27|Well 1,3,4,9,12,15|250,626||||1.2|||||| |28|Well 1,3,4,9,12,15|245,402|||20.00|1.1|||||| |29|Well 1,3,4,9,12,15|243,607|||20.00|1.1|||||| |30|Well 1,3,4,9,12,15|233,659||||1.1|||||| |31|Well 1,3,4,9,12,15|255,543|||40.00|1.1|||||| ||||||||||||| |Total||7,484,117|||300||||||| |AVG.||241,423||#DIV/0!|9.6|1.0|#DIV/0!|#DIV/0!|#DIV/0!|#DIV/0!|| ||||||||||||| Chlorine Mix Ratio = 5 quarts/gallons of 12.5 % chlorine added to
gallons of water in crock Reported by: Fernando Dongo Title: Operator NYS DOH Operator Certification Number: NY0038297 Signature: Date: 11/1/2024 Operator Grade Level IIA, IIB, C, D Verified by pdfFiller 11/04/2024
==> picture [470 x 50] intentionally omitted <==
----- Start of picture text -----
Chlorine Mix Ratio = 5 quarts/gallons of 12.5 % chlorine added to - gallons of water in crock Reported by: Fernando Dongo Title: Operator NYS DOH Operator Certification Number: NY0038297 Verified by pdfFiller 11/04/2024 Signature: Date: 11/1/2024 Operator Grade Level IIA, IIB, C, D ----- End of picture text -----
DOH-360 (02/05) Page 1 of 2
==> picture [4 x 6] intentionally omitted <==
----- Start of picture text -----
0 ----- End of picture text -----
Village of Red Hook Water Treatment 7467 South Broadway, Red Hook, New York 12571
==> picture [37 x 6] intentionally omitted <==
----- Start of picture text -----
11/01/2024 ----- End of picture text -----
==> picture [416 x 168] intentionally omitted <==
----- Start of picture text -----
Water System Water System Notes: Monthly Total Coliform All results absent for the month Deficiencies Town/Village Interconnect 2020 test indicated this was not a viable option for Village flow in case of emergency. Engineering review currently in place. Well Level/Flow Avanti needs to Adjust boosters so they alternate every 24 hours. ----- End of picture text -----
==> picture [49 x 6] intentionally omitted <==
----- Start of picture text -----
For Future Notes: ----- End of picture text -----