TOWN OF RED HOOK WATER DISTRICT NO. 1 Public Water System ID: NY 1302788 May 18, 2023 Work Session Summary April 2023 Monthly Reports

Attendees:

Hank Van Parys, Chairman, Doreen Buono, Ferando Dongo, Jerry Gilnack Bill Hamel

Monthly Items

Normal

April 2023

Water Pumped

6.45 Kgpd

6.34 Kgpd

  1. Well levels:

Well 1 – Well 2 –

41.9 Running 33.0 Running

Well 1 Well 2 -

49.7 Resting 35.7 Resting

Note: Well Levels are the number of feet of water above the pump. Pumps are at different levels 2. Pump Volumes: Well # 1 Well # 2 3. Coliform Report

  1. Turbidity (NTU)

  2. Chlorine Residual

Page 1 of 3

Pumping @ Pumping @ none detected

90 92

GPM GPM

NONE

<1.0 required .05 NTU* *(Nepthalometric Turbitdity Units) <1.0 goal

0.7 PPM* *(parts per Million)

Ongoing Items: 

2023 Water Test Requirements: PFOS - yearly due by 12/31/23 PFOA - yearly due by 12/31/23 DIOXANE - yearly due by 12/31/23 Asbestos - every 9 Yrs. due in 12/2030 Lead, Copper - every 3 years due by 9/30/24 (10 Sites between 6/3 & 9/3) Nitrate - yearly due by 12/31/23 POC & MTBE - yearly due by 12/31/23 Inorganics - yearly due by 12/21/2023 Radiological every 9 years due by 12/31/2030 Disinfection by-products: THMS - yearly HAA5 - yearly

due by 7/1/23 – 9/30/23 due by 12/31/23

Current Inventory: We have 11 5 Micron filter cartridges in stock. We have 11 1 Micron filter cartridges in stock. Top-seals in stock = 7 Filters to be replaced week of 5/22/23 & reordered SODIUM HYPOCHLORITE (chlorine) current supply: IN 5 GALLON CONTAINERS: Empty = 13/ Full = 19

Page 2 of 3

Status:

Ongoing items continued”:

Storage Tank: At the January Water Board Meeting, the board decided the best approach is to rebuild vs. Rehab. Details are in the minutes of the meeting, which are being reviewed by the Water Board members.

Biofilm Build Up in the Tank: This was also discussed at the Water Board Meeting. Fernando did switch to timer control for a few days to allow higher pump volumes. He tested the resulting overflow for chlorine residual. The result was okay. He will do this monthly. The long-range solution is to purchase and install tank-to-pump communication, either radio or cellular. Dan Valentine will prepare an RFP. We will have the tank inspected in 2025 to ascertain if/when we should purchase a new tank.

Valve Installation: Fernando will look into the installation of a valve in the water main in the Manor/Colonial area. He will also think about how to locate galvanized pipe on south side of Aspinwall. This pipe is no longer used but, is still connected to the water main on the north side. This pipe has leaked in the past, se we should find and disconnect it. Fernando overflowed and checked the chlorine. It was ok. We will repeat in a couple of weeks.

Repair: There was a major leak at Albie & Fir. Two small saddels and connections were replaced.

New Connection: A new connection at Victory Lane off North Drive requires a special meter pit. Long lead times for these! Fernando may be able to find an available pit.

Page 3 of 3