Village of Red Hook Water & Wastewater Treatment
7467 South Broadway, Red Hook, New York 12571
02/02/2023
| Water System | Water System | Wastewater System |
|---|---|---|
| Water System Notes: | Wastewater System Notes: Sample results for December 2022, with reporting submitted on | |
| or before January 28, 2023. | ||
| Monthly Total Coliform | All monthly coliform tests were completed | December 2022 |
| - | with no presence of coliform or e. coli | Required Samples |
| - | - | Result |
| - | - | Compliance |
| - | - | BOD |
| - | - | <4.0 |
| - | - | TSS |
| - | - | 2.3 |
| - | - | 10 mg/L |
| - | - | NH3 |
| - | - | <0.5 |
| - | - | 1.81 mg/L |
| - | - | Fecal Coliform |
| - | - | <1.0 |
| - | - | 200/100 mL |
| Deficiencies | - | Deficiencies |
| Well Control Issues | - | Anoxic Mixers |
| Well controls need to be evaluated as communication issues | - | Currently a Medora mixer in place to keep Anoxic tank solids |
| have occurred. Delaware Engineering is presenting to new | - | moving. May need to consider this in future updates. |
| Town/Village Interconnect | - | Sand Filter Rebuild |
| 2020 test indicated this was not a viable option for Village | - | Sand Filters have never been rebuilt or media replaced. Should |
| flow in case of emergency. Engineering review currently in | - | price and schedule for the near future. |
| l | - | Train Down for Review |
| Well Level/Flow | - | One process train is down for review of deficiencies. Review to |
| Well level monitors have been reviewed with a variety of | - | be completed this week and sent for review. |
| repairs that were required. Currently looking at options for | - | Blower System Maintenance |
| communication to wells 14 & 15 as there is a short in wiring | - | Parts have been ordered. Waiting for oil & belts. |
| between the plant and the wells | - | Pump Station |
| Storage Tank Inspections | - | Pump Station pumps clogging issues have been an issue for |
| All storage tanks have been inspected and are awaiting | - | some time. Pump Station mixing should be implemented to |
| report. | - | help with pump failure and pump station pump outs. |
| - | - | Backflow Prev. Replacement |
| - | - | Facilities backflow Preventor in need of replacement. |
| For Future Notes: |
For Future Notes:
Microbiological Sample Resul
NEW YORK STATE DEPARTMENT OF HEALTH
Water Systems Operation Repor
Bureau of Water Supply Protection
==> picture [449 x 554] intentionally omitted <==
----- Start of picture text -----
Public Water System Name Reporting Month/Year Date Report Submitted Source Water Type(s) Village of Red Hook Jan-23 2/1/23 ☐Surface ☒Ground☐GWUDI Public Water System ID County Town, Village, or City ☐Purchase with subsequent chlorination NY1302775 Dutchess Red Hook ☐Purchase w/out subsequent chlorination Chlorination Comments/Observations Treated water Liquid Free chlorine DATE Source(s) in Use volume Hypochlorite added entry point residual at (1,000/day) to crock (quarts) (mg/l) Well 1 1,3,4,9,12,13,14,1 158.7 0.8 Well 2 1,3,4,9,12,13,14,1 231.4 20.00 0.8 5 Well 3 1,3,4,9,12,13,14,1 266.4 0.9 Well 4 1,3,4,9,12,13,14,1 214.7 40.00 0.9 Well 5 5 1,3,4,9,12,13,14,1 169.8 1.0 Well 5 6 1,3,4,9,12,13,14,1 192.1 20.00 1.1 Well 5 7 1,3,4,9,12,13,14,1 196.6 1.2 5 Well 8 1,3,4,9,12,13,14,1 253.5 1.2 9 1,3,4,9,12,13,14,1Well 145.5 20.00 1.3 Well 10 1,3,4,9,12,13,14,1Well 190.4 1.3 11 1,3,4,9,12,13,14,1 196.6 40.00 1.3 12 1,3,4,9,12,13,14,1Well Well 5 196.0 1.3 13 1,3,4,9,12,13,14,1 199.5 20.00 1.2 5 Well 14 1,3,4,9,12,13,14,1 182.8 1.4 Well 15 1,3,4,9,12,13,14,1 271.7 1.3 Well 16 1,3,4,9,12,13,14,1 177.4 20.00 1.3 5 Well 17 1,3,4,9,12,13,14,1 226.6 1.3 18 1,3,4,9,12,13,14,1Well 205.9 40.00 1.3 Well 19 1,3,4,9,12,13,14,1 189.1 1.4 20 1,3,4,9,12,13,14,1Well 193.6 20.00 1.4 21 1,3,4,9,12,13,14,1Well 196.3 1.4 Well 22 1,3,4,9,12,13,14,1 241.5 1.3 23 1,3,4,9,12,13,14,1Well 170.5 1.2 24 1,3,4,9,12,13,14,1Well 191.1 40.00 1.3 25 1,3,4,9,12,13,14,1Well 171.5 1.2 26 1,3,4,9,12,13,14,1Well 187.6 1.1 27 1,3,4,9,12,13,14,1Well 200.4 32.00 1.2 Well 28 1,3,4,9,12,13,14,1 155.3 1.2 29 1,3,4,9,12,13,14,1Well 249.8 1.3 30 1,3,4,9,12,13,14,1Well 193.4 8.00 1.2 31 1,3,4,9,12,13,14,1Well 155.2 1.2 Total 6,171.1 300 AVG. 199.1 #DIV/0! 9.6 1.2 #DIV/0! #DIV/0! #DIV/0! #DIV/0! ----- End of picture text -----
==> picture [446 x 45] intentionally omitted <==
----- Start of picture text -----
Chlorine Mix Ratio = 5 quarts/gallons of 12.5 % chlorine added t - gallons of water in crock Reported by Fernando Dongo Title: Operator NYS DOH Operator Certification Number NY0038297 Signature: Date: 2/1/2023 Operator Grade Level IIA, IIB, C, D ----- End of picture text -----
DOH-360 (02/05) Page 1 of 2
Village of Red Hook Water Treatment Facilities Monthly Report
February 2, 2023
System Flow
During the month of January, the water treatment facility treated 6,171,100 total gallons, which is an average of 199,100 gallons per day. See below for the Annual Daily Average Flow Chart:
All bacteriological samples for the month were collected and transported to Pace Analytical Services, Newburgh, New York. Please see below for sample locations and results:
| Location | Total Coliform | E. Coli |
|---|---|---|
| 7331 S. Broadway | Absent | Absent |
| 7519 N. Broadway | Absent | Absent |
| Mail Room Traditions | Absent | Absent |
Chemical Usage
During the month of January, the water treatment plant used 75 gallons of sodium hypochlorite. The average daily use was 2.4 gallons per day.
If you should have any questions in regards to this report, please feel free to reach out to me at our main office at (845) 244-0129 or by email at Fernando@C3NDEnviro.com
a
Sincerely, Fernando Dongo Principal Consultant C3ND Environmental Consulting