Red Hook WatchIndependent Community Resource

Village of Red Hook Water Treatment Facilities Monthly Report — March 5, 2025

Meetings/Documents/att::2025-03-10_minutes_663__b05
Attached document2025-03-10

Village of Red Hook Water Treatment Facilities Monthly Report

March 5, 2025

System Flow

During the month of February the water treatment facility treated 6,809,761 total gallons, which is an average of 243,206 gallons per day. See below for the Annual Daily Average Flow Chart:

==> picture [433 x 127] intentionally omitted <==

All bacteriological samples for the month were collected and transported to York Analytical, Newton, Connecticut. Please see below for sample locations and results:

LocationTotal ColiformE. Coli
12 Church Street ExtAbsentAbsent
2 W. Market St.AbsentAbsent
7331 S. BroadwayAbsentAbsent

Chemical Usage

During the month of February 2025, the water treatment plant used 75 gallons of sodium hypochlorite. The average daily use was 2.67 gallons per day.

If you should have any questions in regards to this report, please feel free to reach out to me at our main office at (845) 244-0129 or by email at Fernando@C3NDEnviro.com

Sincerely, Fernando Dongo Principal Consultant C3ND Environmental Consulting

==> picture [474 x 479] intentionally omitted <==

----- Start of picture text -----

Village of Red Hook Water Treatment 7467 South Broadway, Red Hook, New York 12571 03/01/2025 Water System Water System Notes: Monthly Total Coliform All results absent for the month Deficiencies Town/Village Interconnect 2020 test indicated this was not a viable option for Village flow in case of emergency. Engineering review currently in place. For Future Notes: ----- End of picture text -----

NEW YORK STATE DEPARTMENT OF HEALTH Bureau of Water Supply Protection

Water Systems Operation Report Microbiological Sample Results

==> picture [477 x 630] intentionally omitted <==

----- Start of picture text -----

Public Water System Name Reporting Month/Year Date Report Submitted Source Water Type(s) Village of Red Hook Feb-25 3/1/25 ☐Surface ☒Ground ☐GWUDI Public Water System ID County Town, Village, or City ☐Purchase with subsequent chlorination NY1302775 Dutchess Red Hook ☐Purchase w/out subsequent chlorination Chlorination Comments/Observations Treated water Liquid Free chlorine DATE Source(s) in Use volume Hypochlorite added to crock residual at entry (gallons/day) (quarts) point (mg/l) Well 1,3,9,12,13,14,15 0.89 1 259,447 Well 1,3,9,12,13,14,15 0.86 2 245,519 Well 1,3,9,12,13,14,15 20.00 0.84 3 249,578 Well 1,3,9,12,13,14,15 0.85 4 243,237 Well 1,3,9,12,13,14,15 36.00 0.88 5 242,922 Well 1,3,9,12,13,14,15 0.92 6 232,415 Well 1,3,9,12,13,14,15 0.93 7 248,835 Well 1,3,9,12,13,14,15 0.93 8 247,875 Well 1,3,9,12,13,14,15 0.93 9 240,730 Well 1,3,9,12,13,14,15 40.00 0.93 10 243,287 Well 1,3,9,12,13,14,15 0.93 11 241,886 Well 1,3,9,12,13,14,15 20.00 0.95 12 241,438 Well 1,3,9,12,13,14,15 0.99 13 237,437 Well 1,3,9,12,13,14,15 40.00 1 14 196426 Well 1,3,9,12,13,14,15 0.97 15 238884 Well 1,3,9,12,13,14,15 0.94 16 202711 Well 1,3,9,12,13,14,15 0.91 17 249259 Well 1,3,9,12,13,14,15 40.00 0.91 18 260345 Well 1,3,9,12,13,14,15 0.89 19 258233 Well 1,3,9,12,13,14,15 0.88 20 245186 Well 1,3,9,12,13,14,15 40.00 0.88 21 287960 Well 1,3,9,12,13,14,15 0.92 22 231736 Well 1,3,9,12,13,14,15 0.94 23 256532 Well 1,3,9,12,13,14,15 20.00 0.96 24 226770 Well 1,3,9,12,13,14,15 0.91 25 230182 Well 1,3,9,12,13,14,15 40.00 0.88 26 242125 Well 1,3,9,12,13,14,15 0.94 27 228460 Well 1,3,9,12,13,14,15 20.00 0.91 28 280346 Well 1,3,9,12,13,14,15 29 Well 1,3,9,12,13,14,15 30 Well 1,3,9,12,13,14,15 31 Total 6,809,761 300 AVG. 243,206 #DIV/0! 9.6 0.9 #DIV/0! #DIV/0! #DIV/0! #DIV/0! Chlorine Mix Ratio = 5 quarts/gallons of 12.5 % chlorine - gallons of water in crock Reported by: Well 1,3,9,12,13,14,15 Title: Operator NYS DOH Operator Certification Number: NY0038297 Signature: Date: 3/1/2025 Operator Grade Level IIA, IIB, C, D ----- End of picture text -----

DOH-360 (02/05) Page 1 of 2

Microbiological Samples and Free Chlorine Residual

==> picture [479 x 408] intentionally omitted <==

----- Start of picture text -----

Sample Total Population Served: 2830 Sample Location SampleDate of 1.Routine 2.RepeatType Coliform Positive PositiveE.coli Residual (mg/l)Free Chlorine Number of microbiological monitoring samples required 3 12 Church Street Ext 2/5/2025 1 Absent Absent 0.2 Bathroom Sink Number of microbiological monitoring samples taken: 3 Did an M&R violation 2 W. Market St. 2/5/2025 1 Absent Absent 0.2 If “Yes,” check reason (s) below: 7331 S. Broadway 2/5/2025 1 Absent Absent 0.8 Actual number of samples is fewer than required. Did not collect/analyze repeat sample. Did not collect/analyze for E. coli for positive total coliform from routine/repeat sample. Did an MCL violation occur? If “ Yes ,” check reason(s) below (see also Part 5, Table 6 for additional information). For systems collecting less than 40 samples per month: two or more of the samples (routine and /or repeat) are positive for total coliform (= total coliform MCL violation). For systems collecting 40 or more samples per month: more than 5% of the samples (routine and/or repeat) are positive for total coliform (= total coliform MCL violation). The original sample was E.coli positive and at least 1 repeat sample was positive for total coliform ( = E.coli MCL violation). Reminder: System must collect a minimum of five (5) routine microbiological monitoring samples during the month following a repeat sample collection. As required by 5-1.72, “Operation of a Public Water System,” a copy of this form shall be sent to your local health department by the 10th calendar day of the next reporting period. ----- End of picture text -----

Sample Collector(s) Fernando Dongo

Name of NYSDOH Certified Lab York Analytical

Did any MCL violation occur? If so, please d No

Did an emergency or low pressure problem occur? Did source water bypass an existing treatment process in the system?If so, please explain.

Comments

DOH-360 (02/05) Page 2 of 2