Red Hook WatchIndependent Community Resource

Red Hook Commons Wastewater System Summary — December 2023

Meetings/Documents/att::2024-02-12_minutes_432__b13
Attached document2024-02-12

|Ni eS Ld

Consulting
Village of Red Hook Wastewater System
Red Hook CommonsVillage of Red Hook
Average Daily Flow :0.014 MGD (Million Gallons per Day)0.039 MGD (Million Gallons per Day)
Required SamplesResultCompliance
BOD (June 1 - Oct 31)<4.0 mg/L5 mg/L
December 2023TSS
NH3<10 mg/L
<0.50
0.98 mg/L (June 1 - Oct 31) 1.81 mg/L (Nov 1 - May 31)10 mg/L
0.98 mg/L (June 1 - Oct 31) 1.81 mg/L (Nov 1 - May 31)
Fecal Coliform<1.0/100 mL200/100 mL
Dissolved Oxygen8.0 mg/L
7.0 mg/L Minimum
Deficiencies
Anoxic MixersCurrently a Medora mixer in place to keep Anoxic tank solids moving. May need to consider this in future updates.
Sand Filter RebuildSand Filters have never been rebuilt or media replaced. Should price and schedule for the near future.
Train Down for ReviewReviewed Train and found air getting into the aeration tank. Currently working on pricing for replacement parts. Train scheduled to go back online on 1/8/2024
Pump StationPump Station pumps clogging issues have been an issue for some time. Pump Station mixing should be implemented to help with pump failure and pump station pump outs.Pump Station pumps clogging issues have been an issue for some time. Pump Station mixing should be implemented to help with pump failure and pump station pump outs.
Backflow Prev.Facilities backflow Preventor in need of replacement.
R
l
Additional Notes: