NYS DEC Wastewater Facility Operation Report — Village of Red Hook Sewer — February 2025

Meetings/Documents/wwtpb::wwtp_dc_1741_2025_february_sewer__b00
Attached document2025-02-28

||Na 38"‘onmental Consulting||||||||||||| |---|---|---|---|---|---|---|---|---|---|---|---|---|---| ||||||Village of Red Hook Wastewater System||||||||| ||||Red Hook Commons|||||||Village of Red Hook|||| |Average Daily Flow :|||0.007 MGD (Million Gallons per Day)|||||||0.036 MGD (Million Gallons per Day)|||| |||||Required Samples|||Result- Old Plant|||Result- New Plant||Compliance|| |||||CBOD||||15 mg/L||62 mg/L||5 mg/L|| |||||TSS||||13.7 mg/L||110 mg/L||10 mg/L|| ||February 2025|||NH3||||4.9||58.2|0.98 mg/L (June 1 - Oct 31) 1.81 mg/L (Nov 1 - May 31)||| |||||Fecal Coliform||||2420/100 mL||2420/100 mL||200/100 mL|| |||||Dissolved Oxygen||||2.0 mg/L||2.3 mg/L|7.0 mg/L Minimum||| |||||TKN||||7.8mg/L||58.2mg/L|0.4 mg/L Minimum||| |||||||Deficiencies||||||||

Sand Filter - Red Hook Commons Sand Filters have never been rebuilt or media replaced. To be reviewed and incorporated into the planning for the Sewer Phase II project.

Backflow Prev. Replacement - Facilities backflow Preventor in need of replacement. Red Hook Commons

UV'S - Red Hook Commons & 1 UV on at new plant. C3ND will provide village with pricing on upgraded power supply for the UV system. Ethernet cable was tested and found to be unable to support the energy supply. Awaiting further guidance from Village of Red Hook Enaqua.

Treatment Plant Cleaning Work Completed by Village & C3ND

Additional Notes: