----- Start of picture text -----

Village of Red Hook Wastewater System Red Hook Commons Village ofRed Hook Average Daily Flow : 0.015 MGD (Million Gallons per Day 0.039 MGD (Million Gallons per Day) Required Samples Result Compliance BOD (June 1 - Oct 31) 1.9 mg/L 5me/L February 2024 TSS <2.50mg/L 10 mg/L NH3 <0.50 0.98 mg/L (June 1 - Oct 31) 1.81 mg/L (Nov 1 - May 31) Fecal Coliform <1.00/100 mL 200/100 mL Dissolved Oxygen 8.0 mg/L .o mg/L Minimum Deficiencies Anoxic Mixers Placed Aeration tank back in service, system is working properly Sand Filter Rebuild Sand Filters have never been rebuilt or media replaced. Should price and schedulefor the nearfuture. Train Downfor Review Reviewed Train andfound air getting into the aeration tank. Currently working on pricing for replacement parts. Train scheduled to go back online on 1/8/2024 Pump Station Pump Station pumps clogging issues have been an issuefor same time. Pump Station mixing should be implemented to help with pump failure and pump station pump outs. Backflow Prev. Facilities backflow Preventor in need of replacement. Additional Notes: ----- End of picture text -----