Red Hook WatchIndependent Community Resource

Village of Red Hook Wastewater System Red Hook Commons — September 2024

Meetings/Documents/att::2024-11-04_minutes_645__b09
Attached document2024-11-04

||C Ni gates Consulting|||||||||| |---|---|---|---|---|---|---|---|---|---|---| |||||Village of Red Hook Wastewater System||||||| |||Red Hook Commons|||||Village of Red Hook|||| |Average Daily Flow :||0.008 MGD (Million Gallons per Day)|||||0.038 MGD (Million Gallons per Day)|||| ||||Required Samples||Result- Old Plant||Result- New Plant||Compliance|| ||||BOD (June 1 - Oct 31)||<1.0 mg/L||<21.0 mg/L||5 mg/L|| ||September 2024||TSS NH3||4.40 mg/L <0.05||<2.50 mg/L <0.05|10 mg/L 0.98 mg/L (June 1 - Oct 31) 1.81 mg/L (Nov 1 - May 31)||| ||||Fecal Coliform||<1.00/100 mL||<1.00/100 mL||200/100 mL|| ||||Dissolved Oxygen||7.0 mg/L||7.0 mg/L|7.0 mg/L Minimum|||

Deficiencies

Sand Filter Sand Filters have never been rebuilt or media replaced. To be reviewed and incorporated into the planning for the Sewer Phase II project.

Backflow Prev. Facilities backflow Preventor in need of replacement. Replacement

Additional Notes: