Red Hook WatchIndependent Community Resource

Town of Red Hook Greenway and Trails Committee Monthly Report — March 2024

Meetings/Documents/att::2024-04-08_minutes_443__b09
Attached document2024-04-08

|Ni 34ironmental

Consulting
Village of Red Hook Wastewater System
Red Hook CommonsVillage of Red Hook
Average Daily Flow :0.015 MGD (Million Gallons per Day0.039 MGD (Million Gallons per Day)
Required SamplesResultCompliance
BOD (June 1 - Oct 31)1.3 mg/L5 mg/L
February 2024TSS
NH3<2.50mg/L
<0.5010 mg/L
0.98 mg/L (June 1 - Oct 31) 1.81 mg/L (Nov 1 - May 31)
Fecal Coliform<1.00/100 mL200/100 mL
Dissolved Oxygen8.0 mg/L7.0 mg/L Minimum
Deficiencies
Anoxic MixersPlaced Aeration tank back in service, system is working properly
Sand Filter RebuildSand Filters have never been rebuilt or media replaced. Should price and schedule for the near future.
Train Down for ReviewReviewed Train and found air getting into the aeration tank. Currently working on pricing for replacement parts. Train scheduled to go back online on 1/8/2024
Pump StationPump Station pumps clogging issues have been an issue for some time. Pump Station mixing should be implemented to help with pump failure and pump station pump outs.Pump Station pumps clogging issues have been an issue for some time. Pump Station mixing should be implemented to help with pump failure and pump station pump outs.
Backflow Prev.Facilities backflow Preventor in need of replacement.
R
l
Additional Notes: